Retail · 2025

LED lighting retrofit and circuit reorganisation in a building-supplies store

A 1,850 m² store in Brasilia replaced burnt luminaires like-for-like. I mapped the real illuminance of each sales zone and redesigned the retrofit: the same light level, 34% less installed power and one circuit per department.

Illuminance LED retrofit Load schedule Circuit per department Design + metering
ClientBuilding-materials and farm-supply store (name withheld)
LocationBrasilia, DF
Year2025
Load120 kVA
Area1,850 m²
Standard appliedNBR ISO/CIE 8995-1 · NBR 5410
Duration26 days
Resultthe same illuminance with 34% less installed power
LED lighting retrofit and circuit reorganisation in a building-supplies store

The request was to replace everything with LED

It arrived as a catalogue quote: pull out the 112 fluorescent fittings and fill the store with round panels. The real problem sat elsewhere. Eight circuits mixed the shop front, the aisles and the warehouse, so the manager lit the whole store to open three checkouts. And the board had no protective conductor and no residual current device on the garden side.

What the metering showed

ZoneMeasured illuminanceStandard referencePower beforePower as designed
Shop front310 lx500 lx1,840 W1,120 W
Aisles240 lx300 lx2,560 W1,480 W
Checkouts420 lx500 lx640 W390 W
Warehouse and dock110 lx200 lx1,180 W760 W

With the numbers on the table the job turned small in one place and large in another: 28 fittings were already above the NBR ISO/CIE 8995-1 reference and stayed where they were; circuits were split by department with independent switching and three new RCDs; and the warehouse got occupancy control in the racking aisles. Lighting power fell from 6.2 kW to 4.1 kW with no zone below the required level.

A rule of thumb I did not follow: replace it all. A good retrofit does only what the metering tells you to do, not one fitting more.