Substation upgrade and new main switchboard for a packaging plant
A plant in Guarulhos ran its 1994 substation with no discrimination and no earthing record. I redrew the single-line diagram, the me…
- Ano2025
- Escoposurvey + design
- Entrega23 days
A generation company in Ceara needed the report to renew substation insurance. I measured the mesh under the assumed fault, checked the lightning protection and ranked 21 non-conformities by risk with estimated cost.
The policy was up for renewal subject to a report on the earthing and lightning protection system of the collector substation, which takes power from nine turbines over 34.5 kV lines. The last document dated from commissioning, four years earlier, and carried no real fault current: it used the short-circuit figure from the design sheet, taken before the farm went live.
The mesh passed the resistance criterion and failed the gradient one: three gates and one disconnector control box sat above the admissible limit for the current fault level. The report listed 21 non-conformities, ordered by risk rather than by how visible they were, each with a suggested deadline and a cost band for the fix.
A useful report does not end at the stamp: it ends in a queue of corrections that maintenance can execute in the right order, with the money that actually exists.
A plant in Guarulhos ran its 1994 substation with no discrimination and no earthing record. I redrew the single-line diagram, the me…
A 1,850 m² store in Brasilia replaced burnt luminaires like-for-like. I mapped the real illuminance of each sales zone and redesigne…
A Curitiba condominium approved 48 bays with chargers and the substation could not follow. I ran the load study with the building ma…